Description
Test voltages of 500, 1000, 2500 and 5000V
Measurement up to 1000GΩ
Bar graph indication of test voltage
Output voltage monitor uses rolling average
Output voltage monitor uses routing average
Timer measurement function
Indication of output and discharge voltages
Lock down test button for hands-free testing
Auto-discharge
Voltage output warning system
Back light
Auto power off and Battery check
Complies to IEC61010-1 CAT.III 600V
Additional Information
Accessories
ACC7165 Line probe
ACC7166 Earth probe
ACC7167 Guard probe
Batteries
Carrying strap
Instruction Manual
Certificate of Conformity
Technical Specifications
Range | Insulation Resistance |
Voltage Measurement |
|||
500v | 1000v | 2500v | 5000v | AC/DC V | |
Measuring Range |
0.0 ~ 99.9M 100 ~ 999M |
0.0 ~ 99.9M 100 ~ 999M 1.0 ~ 1.99G |
0.0 ~ 99.9M 100 ~ 999M 1.0 ~ 9.99G 10.0 ~ 99.9G |
0.0 ~ 99.9M 100 ~ 999M 1.0 ~ 9.99 G10.0 ~ 99.9 G100 ~ 1000G(1T) |
30 ~ 600V AC/DC (50/60Hz) |
Accuracy | +5%rdg ± 3dgt | +5%rdg ± 3dgt | +5%rdg ± 3dgt |
+5%rdg ± 3dgt ±20% (100Gor more) |
+2%rdg ± 3dgt |
Short Circuit Current | 1.3mA | ||||
Rated Test Current | 1mA ~ 1.2mA | 1mA ~ 1.2mA | 1mA ~ 1.2mA | 1mA ~ 1.2mA | |
Open Current Circuit | 500V DC +30% - 0% | 1000V DC +20% - 0% | 2500V DC +20% - 0% | 2500V DC +20% - 0% | |
Maximum Display | 999 counts (1000 counts only at 1000G) | 630 Counts | |||
Current Consumption | About 1000mA (during measurement) | 25mA approx | |||
Safety Standard | IEC 61010-1 CAT III 600V Pollution Degree 2 | ||||
Power Supply | DC 12V: R14 x 8 | ||||
Dimensions | 205(L) x 152(W) x 94(D)mm | ||||
Weight | 1.8kg approx. |