For telephone sales and support

01332 343788

Welcome to Invirotech

 

Kewtech KT45

Be the first to review this product

Availability: In stock

£519.00

Overview

Digital Loop / PSC Tester
OR

KT45

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Description

NEW Anti-Trip Technology for full no trip LOOP testing on all RCD types 15mA low current/soft LOOP test Noise override button for high current LOOP test 20, 200 & 2000Ω Loop measurement ranges PSC measurement up to 20kA Displays mains voltage before test Lock-down test button – for hands free testing Protected against phase to phase connection Instant correct wiring status check Complies with BS7671 (Part P)

Additional Information

Accessories KAMP 13 mains lead ACC016E 3 wire distribution board test leads Batteries Test lead pouch Carrying strap Instruction Manual Certificate of Conformity

Technical Specifications

Range

Rated Voltage Rated Current Measuring Range Accuracy
LOOP Normal Measurement 20Ω
230V-15%+10%50Hz 25A 0~20Ω 3%rdg±4dg
200Ω 2.3A 0~200Ω
2000Ω 15mA 0~2000Ω
ATT 20Ω

P-N: 25AN-E:

15mAor less

*Resistance between P-N must be 20Ω or less

0~20Ω 3%rdg±4dgt
200Ω 0~200Ω
PSC Normal Measurement 20kA 25A 0~20kA Decided by LOOP accuracy
2000A 25A 0~2000A
200A 2.3A 0~200A
ATT 20kA

P-N: 25AN-E:

15mAor less

*Resistance between P-N must be 20Ω or less

0~20kA Decided by LOOP (ATT) accuracy
2000A 0~2000A
200A 0~200A
Voltage Measurement 100V~300A50Hz     2%±4dg
Reading Type Average of multiple readings